FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Figure 6-6 Teamwork topology
Table 6-7 Note for the screen
No.
1
2
3
4
5
Issue 01 (2021-01-30)
Operation
Description
On/Off
On indicates that the device is powered on, and Off
indicates shutdown.
01/02/03
Indicates the unit address. The unit with the minimum
address is the master unit and others are all slave units.
NOTE
If the master one offline, the online device with the smallest
address is selected to be the new master.
Active/
Active: An active unit properly responds to control
Standby
requirements.
Standby: A standby unit responds to control requirements
only if an active unit is faulty (critical alarm, shutdown, or
offline) or the active unit cannot meet cooling
requirements.
M/S
M indicates the master unit, and S indicates a slave unit. A
blue icon indicates that the unit is operating, and a gray
icon indicates that the unit is idle.
Frame:
A green frame indicates the unit itself,
green/non-
green
as shown in
A non-green frame indicates other units in the group,
as shown in
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
.
.
109