Huawei FusionCol8000-E240 User Manual page 115

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Paramete
r
Number
of running
air
conditione
rs in this
group
Rotation
function
Rotation
Period
Rotation
time
Forced
rotation
Issue 01 (2021-01-30)
Description
Sets the number of running
units in this group. The
value is an integer ranging
from 1 to the number of
units in this group.
Indicates whether to allow
the smart cooling products
to work as the standby
device in turn, maximizing
their service life.
Number of days for
rotation (1-30).
24 time points in a day:
(0-23).
Indicates whether to enable
forced rotation before the
specified rotation time.
After a forced rotation, the
rotation period starts again.
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
Configuration Rule
The master unit
assigns operating
machines in ascending
order of the group
address. The address
meets the 1-32
requirement. The
remaining units are
automatically
classified as standby
devices.
It is recommended
that the function be
enabled when the
load power is even.
The default value is 7.
The default value is 0.
Set this parameter to
Yes if forced rotation
is required. In normal
cases, retain the
default value No.
Default
Value
2
Disable
7day (s)
0
No
106