Huawei FusionCol8000-E240 User Manual page 103

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Step 4 Set related parameters and tap Next until the controller home screen is displayed.
Table 6-2 Quick Settings parameters
Menu
Settings > Quick
Settings > Select
Language
Settings > Quick
Settings > Date & Time
Settings
Settings > Quick
Settings > Teamwork
Settings
Issue 01 (2021-01-30)
Parameter
Select
Language
Date format
Date settings
Time zone
Time
Teamwork
group No.
System
address
Teamwork
function
Networking
mode
Number of
systems in
this group
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
Setting Guide
Set the language based on the site
requirements.
Set the date display format for the
controller.
Set the date displayed on the
controller.
Set the controller time zone.
Set the time displayed on the
controller.
Set the assigned teamwork group
number.
NOTE
The number of the teamwork group. This
parameter should be the same for all
units in the same teamwork group.
Set the planned unit address.
NOTE
The addresses of units in the same
teamwork group cannot be the same.
Enables or disables the teamwork
function. If the function is disabled,
the unit operates independently. If it
is enabled, the unit operates in a
team with other units.
NOTE
Set this parameter based on onsite heat
load distribution.
Indicates the networking mode for
teamwork control. The networking
mode selected on the screen must
match the actual networking mode.
Otherwise, the teamwork function is
unavailable.
Enter the total number of smart
cooling products in the group.
94