Huawei FusionCol8000-E240 User Manual page 68

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Figure 3-30 Cable terminal connection
Step 5 Route the heating belt and temperature sensor probe through the condensate
drainage hole, wrap the heating belt around the condensate drainpipe, and ensure
that the temperature sensor probe is closely attached to the drainpipe.
Step 6 Use silicone sealant to seal the gaps between the heating belt, cables, pipe, and
wall panels.
Step 7 Use thermal insulation foam to wrap the heating belt and temperature sensor
probe around the pipe.
Step 8 Press the SET button on the electric heater controller for 2s. Within 10s, press
and
----End
Issue 01 (2021-01-30)
NO TE
The cable length is about 11 m, and the cable specification is 3 x 1.5 mm
to set the parameter to 5°C, and press the SET button to save the setting.
Copyright © Huawei Technologies Co., Ltd.
3 System Installation (Building Scenario)
2
.
59

Advertisement

Table of Contents
loading

Table of Contents