Huawei FusionCol8000-E240 User Manual page 168

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Step 4 Remove the refrigerant oil heating belt and ground cable from the compressor.
Step 5 Remove the connection box cover, remove cables from the compressor, and
remove the cable trough.
Step 6 Remove the compressor.
1.
2.
Issue 01 (2021-01-30)
Use a welding torch to separate the welding points for the suction and
discharge pipes from the compressor. After the separation, seal the suction
and discharge outlets immediately.
Figure 8-20 Separating the suction and discharge welding joints
(1) Suction port
NO TICE
After removing the compressor, block the suction inlet and exhaust outlet
immediately to ensure the system cleanness and prevent water from entering.
Use a 13# socket wrench (or solid wrench) to remove the four nut washers
and spring washers that secure the compressor and remove the compressor.
NO TICE
Do not hold the suction inlet and exhaust outlet to move the compressor.
Copyright © Huawei Technologies Co., Ltd.
8 System Maintenance
(2) Discharge port
159