FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Context
Figure 3-27 Reserved terminals for the air dampers
(1) Reserved terminal for the indoor supply air
damper
Procedure
Step 1 Install the motorized damper at the air vent of the unit.
Step 2 Connect the air damper cable terminal and reserved cable terminal, and install the
X504 terminal to the corresponding port.
Step 3 Connect the cables from port 3 in G1 and from port 5 in G2 to port X3.1.
Step 4 Connect the cables from port 3 in G3 and port 5 in G4 to port X3.2.
Figure 3-28 Terminal connection
----End