FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Context
The parameters in this section are for reference only. Set practical parameter
values as required.
Procedure
Step 1 On the home screen, tap
Settings screen.
Figure 6-5 Teamwork setting
Step 2 Set teamwork control parameters.
All teamwork control parameters can be set on the master smart cooling product.
Only Teamwork group No., Smart cooling product address, Enable teamwork
CAN resistor, Teamwork function and Networking mode can be set on slave
smart cooling products. Other parameters of the slave units will be modified by
the master unit synchronously.
Table 6-6 Teamwork setting
Paramete
r
Teamwork
group No.
Air
conditione
r address
Issue 01 (2021-01-30)
> Teamwork Settings to enter the Teamwork
Description
The number of the
teamwork unit, which is the
same for all the team unit
numbers in the same group.
Smart cooling product
addresses should be
different from each other.
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
Configuration Rule
Set the assigned
teamwork unit
number.
Set the planned
teamwork unit
address.
Default
Value
1
NA
104