Huawei FusionCol8000-E240 User Manual page 95

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Step 3 Set DIP switches of the T/H sensors.
Table 4-7 DIP switch settings on T/H sensors
Locati
on
Air
return
side
Outdo
or
intake
air
Cold
aisle
Hot
aisle
Issue 01 (2021-01-30)
NO TE
● Each smart cooling product supports a maximum of twelve T/H sensors outside the
cabinet, including a maximum of six cold aisle T/H sensors and six hot aisle T/H sensors.
● It is recommended that the total length of the cable required for the T/H sensors
outside the cabinet be less than or equal to 150 m. If the cable length is greater than
120 m, obtain 12 V DC power from the site to supply power to the T/H sensors that are
120 m or further away from the cabinet. Ensure that the input voltage of each T/H
sensor ranges from 9 V to 16 V.
● The T/H sensors outside the cabinet must be connected to a Category 5E cable or a
network cable with higher specifications. Otherwise, the power supply voltage of the
T/H sensors may be insufficient due to large impedance of the network cable. When the
voltage is less than 9 V, the T/H sensors cannot work properly.
Display Name
Return air 2
temp/humid
Outdoor intake
air 1 temp/
humid
Outdoor intake
air 3 temp/
humid
Cold aisle 1
temp/humid
Cold aisle 2
temp/humid
Cold aisle 3
temp/humid
Cold aisle 4
temp/humid
Cold aisle 5
temp/humid
Cold aisle 6
temp/humid
Hot aisle 1
temp/humid
Hot aisle 2
temp/humid
Copyright © Huawei Technologies Co., Ltd.
4 System Installation (FDC Scenario)
Add
DIP Switch No.
ress
1
2
1
ON
OFF
31
ON
ON
32
OFF
OFF
11
ON
ON
12
OFF
OFF
13
ON
OFF
14
OFF
ON
15
ON
ON
16
OFF
OFF
21
ON
OFF
22
OFF
ON
3
4
5
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
ON
6
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF