3. Allow/suppress display of negative gas measured values in the main view: "Negative
values" parameter field.
– Authorize access with Standard PIN.
– Select "Allow" or "Suppress".
4. Specify the number of displayed measured-value decimal places: "Decimal places"
parameter field.
The setting has an effect on the measured-value display and the extended measured-
value display in the main view.
– Select 0, 1, 2 or 3 decimal places.
– If the measured value gets so big that the full display of the set decimal places is no
5. Set additional parameters or log off manually.
6.2.2

Setting the extended measured-value display

Procedure
You can use this function to display additional information for individual components that
cannot be displayed in the measured-value display.
1. Main menu > "2 Settings" > "01. Display/USER FUNC key" > "2. Extended measured-
value display"
2. Call the parameter display: Press <Enter>.
The parameter display lists all components in the device.
3. Set the display:
– Select and open the parameter field of a component.
– Authorize access with Standard PIN, if necessary.
– Select settings "Hide" or "Show".
4. Set the extended measured-value display of additional components.
Operating with the Local User Interface
Operating Manual, 06/2017, A5E31930478-05
If you select the "Suppress" setting, a value which is actually negative is displayed in
the main view as "0".
This behavior can also be mapped by means of an analog output. You can find more
information on this topic under: [2.09.2] Analog output (Page 141).
longer possible, the decimal point is shifted by one position to the right.
If you select the "Hide" setting, the measured value is not listed in the extended
measured-value display.
However, the measured value is retained in the measured-value display of all
components.