Huawei FusionModule2000 Maintenance Manual page 103

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Maintenance Guide
Figure 5-44 Installing a T/H sensor
Step 6 Set the DIP switches of T/H sensors.
Table 5-9 DIP switch setting on a T/H sensor
Locati
on
Air
return
side
Cold
aisle
Issue 02 (2022-07-30)
Display Name
Return air 2
temp/humid
Cold aisle 1
temp/humid
Cold aisle 2
temp/humid
Cold aisle 3
temp/humid
Cold aisle 4
temp/humid
Cold aisle 5
temp/humid
Copyright © Huawei Digital Power Technologies Co., Ltd.
Addr
DIP Switch Sequence No.
ess
1
2
1
ON
OFF
11
ON
ON
12
OFF
OFF
13
ON
OFF
14
OFF
ON
15
ON
ON
5 Parts Replacement
3
4
5
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
6
OFF
OFF
OFF
OFF
OFF
OFF
96