Huawei FusionModule2000 Maintenance Manual page 41

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Maintenance Guide
Item
Wet film
humidifier
Table 3-7 Quarterly maintenance for the management system
Item
Battery
management
parameter
settings
Issue 02 (2022-07-30)
Method
Start the
equipment,
choose Maint
> Diagnostic
Mode > Enter
on the main
screen, and
start the wet
film
humidifier.
Method
On the UPS
LCD, choose
System Info >
Settings >
Battery
Param. and
check whether
battery
management
parameters
are set as
required.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Expected Result
Water drainage is
normal.
Expected Result
The parameters are
set based on
requirements.
3 Routine Maintenance
Troubleshooting
● If no water is
supplied, check
the cable
connection or
replace the water
inlet solenoid
valve.
● If no water is
supplied to the
wet film
humidifier, check
the cable
connection to the
water pump or
replace the
humidifier water
pump.
Troubleshooting
Set parameters
correctly.
34