Huawei FusionModule2000 Maintenance Manual page 52

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Maintenance Guide
Item
Availability
of the
FusionModul
e Actuator
and skylight
magnetic
lock
Availability
of the access
actuator
Availability
of the access
control
system
Issue 02 (2022-07-30)
Method
On the ECC800-
Pro WebUI,
choose
Monitoring >
Aisle > Fusion
Module Actuator
Group > Fusion
Module
Actuator. On the
Running Control
page, remotely
open the skylight.
NOTE
If you open the
skylight remotely
for maintenance,
manually close the
skylight after the
maintenance is
complete.
On the ECC800-
Pro WebUI,
choose
Monitoring >
Aisle > Access
Actuator Group
> Access
Actuator. On the
Running Control
page, remotely
open doors.
Press the exit
button to open
the door.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Expected Result
The FusionModule
Actuator controls
the skylight in the
aisle of the smart
module.
The access actuator
can be used to
open the aisle doors
of the smart
module.
The door can be
opened by pressing
the exit button.
3 Routine Maintenance
Troubleshooting
If the skylight cannot
be normally
controlled, check
whether the cable
between the skylight
magnetic lock and
FusionModule
Actuator is in good
condition and
securely connected. If
the fault persists,
replace the
FusionModule
Actuator or skylight
magnetic lock.
If an aisle door
cannot be normally
controlled, check
whether the
magnetic lock cable
is loose or
disconnected. If so,
reconnect the cable.
If not, replace the
access actuator or
magnetic lock.
If the door cannot be
opened by pressing
the exit button after
other devices in the
access control system
are normal, replace
the exit button.
45