Technical Specifications - Siemens SIDOOR ATD4 W Series System Manual

Automatic door control units
Table of Contents

Advertisement

7.4.3

Technical specifications

Core statement
Order number
Product
Power supply, type
Input
Input
Rated voltage value Vin rated
Voltage range AC
Wide-range input
Mains buffering at Iout rated, min.
Rated line frequency 1
Rated line frequency 2
Rated line range
Input current
Switch-on current limiting (+25 °C), max.
I²t, max.
Built-in incoming fuse
Protection in the mains power input (IEC 898)
Output
Output
Rated voltage Vout DC
Total tolerance, static ±
Static mains compensation, approx.
Static load balancing, approx.
Residual ripple peak-peak, max.
Spikes peak-peak, max. (bandwidth: 20 MHz)
Adjustment range
Product function Output voltage adjustable
Output voltage setting
Status display
Signaling
On/off behavior
Startup delay, max.
Voltage increase time of the output voltage max‐
imum
Rated current value Iout rated
Current range
ATD4xxW for industrial applications
System Manual, 06/2022, A5E51901827B AA
at rated input voltage 400 V
at rated input voltage 500 V
7.4 SITOP PSU8200 13A/36V 3-phase
6EP3446-8SB10-0AY0
SITOP PSU8200
36 V/13 A
3-phase AC
400 ... 500 V
320 ... 575 V
Yes
15 ms; at Vin = 400 V
50 Hz
60 Hz
47 ... 63 Hz
1.2 A
1 A
16 A
0.8 A²·s
none
Required: 3-pole connected miniature circuit break‐
er 6 ... 16 A characteristic C or circuit breaker
3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10
(UL 489)
Controlled, isolated DC voltage
36 V
3 %
0.1 %
0.2 %
100 mV
200 mV
36 ... 42 V
Yes
via potentiometer; max. 480 W
Green LED for 36 V OK
Relay contact (NO contact, rating 60 V DC/ 0.3 A)
for 36 V OK
No overshoot of Vout (soft start)
2.5 s
500 ms
13 A
0 ... 13 A
Power supply
261

Hide quick links:

Advertisement

Table of Contents
loading