DIP switches (S501)
The DIP switches (S501) on the device are used to set the PROFIBUS address of the DP slave.
①
②
③
④
Figure 5-2
Setting the address
The individual DIP switches 1 to 7 (
reserved.
Addresses within the range from 0 to 127 can be set with combinations of the seven DIP switches
①
(
,
Note
A DP slave address change only becomes effective after a power-on reset or system restart.
The following example shows the setting for the address "89":
DIP switches
Status
(0 ≙ off / 1≙ on)
Address
ATD4xxW for industrial applications
System Manual, 06/2022, A5E51901827B AA
Status: 1≙ on
Status: 0 ≙ off
DIP switch without function
DIP switches for setting the address
DIP switches (S501)
②
). The addresses are coded according to BCD code (Binary Coded Decimal).
1
1
④
) are used to specify the address. DIP switch 8 (
2
3
4
0
0
1
89 (≙ 59
Controllers
5.5 Relay and fieldbus interfaces
5
6
1
0
)
hex
③
) is
7
1