The GSD file is provided in various GSDML scheme versions to ensure compatibility with older
configuration tools.
Table 5-15
Scheme
2.31
2.3
2.25
The GSD files are equivalent in terms of the ATD430W controller's functional scope.
PROFINET communication
Besides using the MAC address and the IP address, PROFINET also uses a device name to identify
PROFINET devices. The device name must be unique in the PROFINET network.
Assigning a device name
During commissioning, each PROFINET device is assigned a device name using the
configuration system (node initialization).
The device name is written to the IO device via an IO supervisor using the DCP (Discovery and
Configuration Protocol). The device name is stored retentively in the ATD430W.
If the device is replaced, this operation must be repeated with the replacement device. Since the
name is assigned with the standardized DCP, this step can be performed with any tool (e.g.
SIMATIC Manager or TIA Portal).
Topology-based initialization
Device names can also be assigned by the IO controller based on the topology. This requires the
topology to be structured as planned and all involved devices to fulfill the requirements of class
B (support of LLDP and SNMP) as a minimum. The device must also be set to its factory default
settings (IP address = 0.0.0.0 and device name = "").
Assigning an IP address
For the expansion of an application relationship, each PROFINET device must have an IP address.
To ensure that the right device is accessed online, it is recommended that IP addresses be
assigned to every PROFINET device at the start of the commissioning process. When configuring
the IO system, both the IO controller and the IO devices are assigned an IP address by the
configuration tool. The IO controller receives an IP assignment list via the system configuration.
The IP addresses are assigned to the IO devices on initialization of the application relationships.
The IO device ATD430W offers the possibility of having the IP address assigned by the IO
controller. This function is activated in many configuration tools by default. For this, there has
to be a PROFINET connection between the IO device and the IO controller and the device name
of the IO device have to agree with the configured device name. When this function is used, a
communication connection to the IO controller must be established so that the IO device is
assigned an IP address and TCP services (e.g. firmware updates) are available.
ATD4xxW for industrial applications
System Manual, 06/2022, A5E51901827B AA
GSD files
GSD file
GSDML-V2.31-Siemens-SIDOOR-TD430W-20140829.xml
GSDML-V2.3-Siemens-SIDOOR-TD430W-20140829.xml
GSDML-V2.25-Siemens-SIDOOR-TD430W-20140829.xml
Controllers
5.5 Relay and fieldbus interfaces
151