Mitsubishi Electric FR-A700 Technical Manual page 107

Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Name
This function stops the inverter output if
communication between the inverter and
PU is suspended, for example the
operation panel and parameter unit is
disconnected, when 2, 3, 16 or 17 was
set in [Pr. 75 Reset selection/disconnected
PU detection/PU stop selection].
This function stops the inverter output
when communication errors occurred
PU disconnection
consecutively for more than permissible
number of retries when [Pr. 121 Number of
PU communication retries
the RS-485 communication with the PU
connector.
This function also stops the inverter
output if communication is broken for the
period of time set in [Pr. 122 PU
communication check time interval].
If operation cannot be resumed properly
Retry count excess
within the number of retries set, this function
trips the inverter.
Stops the inverter output if the
CPU Fault
communication fault of the built-in CPU
occurs.
When the operation panel power supply (PU
connector) is shorted, this function trips the
inverter. At this time, the operation panel
(parameter unit) cannot be used and RS-485
Short circuit of
communication from the PU connector cannot
power supply for
be made.
operation panel,
When the internal power supply for RS-485
power supply for
terminals are shorted, this function shuts off the
RS-485 terminals
power output. At this time, communication from
the RS-485 terminals cannot be made.
To reset, enter the RES signal or switch power
OFF, then ON again.
When the 24VDC power output from the
terminal PC is shorted, this function shuts
off the power output. At this time, all external
24VDC power
contact inputs switch OFF. The inverter
output short circuit
cannot be reset by entering the RES signal.
To reset it, use the operation panel or switch
power OFF, then ON again.
Because [Pr.167 Output current detection
Output current
operation selection] is set to the alarm stop
detection value
setting (=1), this function is activated when
exceeded
the output current exceeds the [Pr. 150
Output current detection level] setting.
This function is activated when the resistor
Inrush current limit
of the inrush current limit circuit overheats.
circuit fault
Activates if the inrush current limit circuit
fault occurs.
Description
9999] during
Indication
Operation
Parameter unit
panel
FR-PU04 FR-PU07
PU Leave Out
(E.PUE)
Retry No Over
(E.RET)
Fault 5
(E.5)
Fault 6
(E.6)
Fault 7
(E.7)
CPU Fault
(CPU)
E.CTE
(E.CTE)
E.P24
(E.P24)
OC
Fault 14
detect
(E.CDO)
level
Inrush
Fault 14
overheat
(E.IOH)
100
SPECIFICATIONS
Available Inverters
A700
F700
E700
D700

Hide quick links: