1.4.20 Output current detection function (Y12, Y13)
[Pr. ]
Name
Output current detection
150
level
Output current detection
151
signal delay time
Zero current detection
152
level
Zero current detection
153
period
Output current detection
166
signal retention time
Output current detection
167
operation selection
Setting
Initial Value
Range
A700
E700 D700
A700
150%
0 to 220%
F700
F700
120%
0 to 150%
E700 D700
0 to 200%
0s
0 to 10s
A700
0 to 220%
5%
F700
0 to 150%
E700 D700
0 to 200%
0.5s
0 to 1s
0 to 10s
0.1s
9999
0
0
1
72
common
(common)
Description
Set the output current detection level.
100% is the rated inverter current.
Set the output current detection
period. Set the time from when the
output current has risen above the
setting until the output current
detection signal (Y12) is output.
Set the zero current detection level.
Suppose that the rated inverter current
is 100%.
Set this parameter to define the period
from when the output current drops
below the [Pr. 152] setting until the zero
current detection signal (Y13) is
output.
Set the retention time when the Y12
signal is ON.
The Y12 signal ON status is retained.
The signal is turned OFF at the next
start.
Operation continues when the Y12
signal is ON.
The inverter is brought to trip (E.CDO)
when the Y12 signal is ON.
SPECIFICATIONS
Available
Inverters
A700
F700
E700
D700