(1) Inverter-generated heat
When the rated output current flows, the inverter
generates heat as shown on the preceding page.
1) Reduction according to motor load factor
At the rated output current, the following figure
shows a reduction rate when operating the
inverter with a light load.
2) Reduction according to duty
The ratio of reduction during intermittent operation
in a cycle of within five minutes is shown.
Indicates motor capacity
100
90
80
70
60
0
20
Load factor versus heat generated
(when motor and inverter have the same rank)
100
75
50
25
0
20
Duty versus heat generated
200V class
Inverter Capacity (kW)
A700
F700
0.4
0.75
0.75
1.5
1.5
2.2
2.2
3.7
3.7
5.5
5.5
7.5
7.5
11
11
15
15
18.5
18.5
22
22
30
400V class
Inverter Capacity (kW)
A700
F700
0.4
0.75
0.75
1.5
1.5
2.2
2.2
3.7
3.7
5.5
5.5
7.5
7.5
11
11
15
15
18.5
18.5
22
22
30
Electricity during standby (at a stop)
40
60
80
100
Motor load factor(%)
40
60
80
100
Duty (%ED)
Standby Electricity (W)
Fan is ON
Fan is OFF
9 (without fan)
9 (without fan)
13
11
13
11
13
11
19
11
19
11
22
14
25
15
25
15
27
15
Standby Electricity (W)
Fan is ON
Fan is OFF
14 (without fan)
14 (without fan)
14 (without fan)
16
14
16
14
23
15
23
15
26
18
26
18
28
18
28
18
546
SELECTION