Mitsubishi Electric FR-A700 Technical Manual page 351

Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

[Pr. ]
Stall prevention operation current
277
*1 *2 *4
switchover
291
Pulse train I/O selection
*2 *3 *4
292
Automatic acceleration/deceleration
*2 *4
Acceleration/deceleration individual
293
*2 *4
operation selection
298
Frequency search gain
*1 *2
Digital input unit selection
329
Parameter for the plug-in option FR-
*4
A7AX
343
Communication error count
450
Second applied motor
*2
451
Second motor control method selection
*2 *3 *4
Second motor capacity
453
*2 *3 *4
454
Number of second motor poles
*2 *3 *4
458 to 462
*2 *3 *4
(second motor constant)
463
Second motor auto tuning setting/status
*2 *3 *4
Frequency command sign selection
(CC-Link)
541
*2 *4
(Parameter for the plug-in option FR-
A7NC)
563
Energization time carrying-over times
564
Operating time carrying-over times
574
*2 *3 *4
Second motor online auto tuning
800
Control method selection
*2
819
Easy gain tuning selection
*2 *3 *4
Terminal 4 function assignment
858
*2 *3 *4
859
Torque current
*2
Second motor torque current
860
*2 *3 *4
868
Terminal 1 function assignment
*2 *3 *4
*1
These are not available for
*2
These are not available for
*3
These are not available for
*4
These are not available for
*5
These parameters can be written while inverter is
running in
A700
2.18.3 Reverse rotation prevention selection [Pr. 78]
This function can prevent reverse rotation fault resulting
from the incorrect input of the start signal. Set this
parameter when you want to limit the motor rotation to only
one direction.
This parameter is valid for all of the reverse rotation and
forward rotation keys of the operation panel (FR-DU07)
and parameter unit (FR-PU04/FR-PU07), the start signals
(STF, STR signals) via external terminals, and the forward
and reverse rotation commands through communication.
Name
.
A700
.
F700
.
E700
.
D700
.
D700
common
(common)
[Pr. ]
Name
Reverse
rotation
78
prevention
selection
385
PARAMETER
Initial
Setting
Description
Value
Range
Both forward and
0
reverse rotations
enabled
0
Reverse rotation
1
disabled
Forward rotation
2
disabled
2