Selection Of Peripheral Devices - Mitsubishi Electric FR-A700 Technical Manual

Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

3.6 Selection of peripheral devices

The moulded case circuit breakers, magnetic contactors and cables differ with the inverter models.
For specific selection, refer to the corresponding model catalog or manual.
Motor
Applied
Output
Inverter
(kW)
Type
*1
0.4
FR-A720-0.4K
0.75
FR-A720-0.75K 30AF 10A
1.5
FR-A720-1.5K
2.2
FR-A720-2.2K
3.7
FR-A720-3.7K
5.5
FR-A720-5.5K
7.5
FR-A720-7.5K
11
FR-A720-11K
15
FR-A720-15K
18.5
FR-A720-18.5K 225AF 150A
22
FR-A720-22K
30
FR-A720-30K
37
FR-A720-37K
45
FR-A720-45K
55
FR-A720-55K
75
FR-A720-75K
90
FR-A720-90K
Peripheral device selection list (example
Moulded Case Circuit Breaker (MCCB)
or Earth Leakage Circuit Breaker (ELB)
Reactor connection
Without
30AF 5A
30AF 15A
30AF 20A
30AF 30A
50AF 50A
100AF 60A
100AF 75A
225AF 125A
225AF 175A
225AF 225A
400AF 250A
400AF 300A
400AF 400A
A700
*2
With
30AF 5A
30AF 10A
30AF 15A
30AF 15A
30AF 30A
50AF 40A
50AF 50A
100AF 75A
100AF 100A
225AF 125A
225AF 150A
225AF 175A
225AF 225A
400AF 300A
400AF 350A
400AF 400A
400AF 400A
526
SELECTION
)
Recommended
Magnetic contactor on
Cable Size
the Input Side
*3
Reactor connection
R, S, T U, V, W
Without
With
S-N10
S-N10
S-N10
S-N10
S-N10
S-N10
S-N10
S-N10
S-N20,
S-N10
3.5
N21
S-N20,
S-N25
5.5
N21
S-N25
S-N25
14
S-N35
S-N35
14
S-N50
S-N50
22
S-N65
S-N50
38
S-N80
S-N65
38
S-N95
S-N80
60
S-N150
S-N125
80
S-N180
S-N150
100
S-N220
S-N180
100
S-N300
125
S-N300
150
2
(mm
)
*4
2
2
2
2
2
2
2
2
3.5
5.5
8
14
22
38
38
60
80
100
100
125
150

Hide quick links: