2.5.5
Shortest acceleration/deceleration and optimum acceleration/deceleration
(automatic acceleration/deceleration) [Pr. 61 to 63, 292, 293]
The inverter operates in the same conditions as when
appropriate values are set in each parameter even if
acceleration/deceleration time and V/F pattern are not set. This
function is useful when you just want to operate, etc. without
fine parameter setting.
Even if automatic acceleration/deceleration mode is selected,
inputting the JOG signal (Jog operation) or RT signal (second
function selection) or X9 signal (third function selection) during
[Pr.]
Name
61
Reference current
Reference value at
62
acceleration
Reference value at
63
deceleration
Automatic
292
acceleration/
deceleration
Acceleration/
deceleration
293
individual operation
selection
Initial
Setting Range
Value
55K or less 0 to 500A Set the reference current during shortest/
75K or more 0 to 3600A
9999
9999
A700
0 to 220%
E700
0 to 200%
9999
9999
A700
0 to 220%
E700
0 to 200%
9999
9999
0
1
11
0
3
,
5
6
7
,
8
0
0
1
2
241
A700 E700
an inverter stop will switch to the normal operation and give
priority to Jog operation or second and third function selection.
Note that JOG and RT signal input is invalid even if JOG signal
and RT signal are input during operation in automatic
acceleration/deceleration mode.
When PID control or load torque high speed frequency control
is selected, optimum acceleration/deceleration is invalid.
Description
optimum acceleration/deceleration.
Rated inverter output current value is
reference
Set the limit value/optimum value during
shortest/optimum acceleration.
Shortest acceleration/deceleration: 150% is a
limit value
Optimum acceleration/deceleration: 100% is
an optimum value
Set the limit value /optimum value during
shortest/optimum deceleration.
Shortest acceleration/deceleration: 150% is a
limit value
Optimum acceleration/deceleration: 100% is
an optimum value
Normal Mode
Shortest acceleration/deceleration (without
brake)
Shortest acceleration/deceleration (with brake)
Optimum acceleration/deceleration
Elevator mode1, 2 (refer to page 249)
Brake sequence mode 1, 2 (refer to page 399)
Both acceleration and deceleration are made
in the shortest (optimum) acceleration/
deceleration mode
Only acceleration is made in the shortest
(optimum) acceleration/deceleration mode
Only deceleration is made in the shortest
(optimum) acceleration/deceleration mode
PARAMETER
(A700)(E700)
Available
Inverters
A700
E700
2