Mitsubishi Electric FR-A700 Technical Manual page 70

Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Setting
Signal
Positive
Negative
Name
logic
logic
41
141
FB
Speed detection
42
142
FB2
Second speed detection
43
143
FB3
Third speed detection
44
144
RUN2
Inverter running 2
Inverter running and start
45
145
RUN3
command is on
During deceleration due to
46
146
Y46
power failure stop function
During PID control
47
147
PID
activated
64
164
Y64
During retry
70
170
SLEEP PID output interruption
80
180
SAFE
Safety monitor output
Position control
84
184
RDY
preparation ready
85
185
Y85
DC feeding
Control circuit capacitor
86
186
Y86
life
*5
87
187
Y87
Main circuit capacitor life
88
188
Y88
Cooling fan life
Inrush current limit circuit
89
189
Y89
*5
life
90
190
Y90
Life alarm
Fault output 3 (power-off
91
191
Y91
signal)
Energy saving average
92
192
Y92
value updated timing
Current average value
93
193
Y93
monitor signal
94
194
ALM2
Fault output 2
95
195
Y95
Maintenance timer signal
96
196
REM
Remote output
97
197
ER
Alarm output 2
Functions
Output when the actual motor speed (estimated actual
speed value) reaches the [Pr. 42 (Pr. 50, Pr. 116)] setting.
• Output during forward rotation or the reverse rotation
signal is ON.
• Output at deceleration even during forward rotation
or the reverse rotation signal is OFF.
(Does not output during pre-excitation LX is ON.)
• Output during the orientation command signal (X22)
is ON.
• Switched ON when the servo is ON (LX-ON) under
position control.
(Switched OFF when the servo is OFF (LX-OFF).
Output when the inverter running and start commands
are ON.
Output when the power failure-time deceleration
function is executed(retained until release).
Output during PID control.
Output during retry processing.
Output when the PID output interruption function is
executed.
Output while safety stop function is activated.
Signal is output when the servo is ON (LX-ON) and
ready to operate.
Output during power failure or under voltage of AC
power.
Output when the control circuit capacitor life falls below
10% of ([Pr. 257]).
Output when the main circuit capacitor life falls below
*5
85% of ([Pr. 258]).
Output when the speed of the cooling fan falls below
*5
50%.
Output when the inrush current limit circuit life falls
below 10% of ([Pr. 256]).
Output when any of the control circuit capacitor, main
circuit capacitor and inrush current limit circuit or the
cooling fan approaches the end of its service life.
Output when a fault occurs due to the internal circuit
failure of the inverter wiring mistake.
Turned ON and OFF alternately every time the power
saving average value is updated when the power
saving monitor is used.
Cannot be set to a relay output terminal.
Average current value and maintenance timer value
are output as pulses.
Cannot be set to a relay output terminal.
Output when the inverter protective function is
activated to stop the output (fault).
Continue outputting the signal during inverter reset and
stop outputting after reset is cancelled.
Output when [Pr. 503] rises to or above the [Pr. 504]
setting.
Output to the terminal when a value is set to the
parameter.
When [Pr. 875 = "0"] (initial value), the signal is output
when the inverter protective function is activated to
stop the output (major fault).
When [Pr. 875 = "1"], the signal is output when the
inverter protective function is activated at occurrence of
OHT/THM/PTC error and deceleration is started.
Output when other protective functions are activated to
stop output.
Operation
*4
*3
63
SPECIFICATIONS
Available Inverters
A700
F700
E700
D700
1