2.8.2
Offline auto tuning function
[ Pr. 71, 80 to 84*, 90 to 94*, 96, 450*, 453 to 463*, 684*, 859*, 860*]
A700 E700 D700
Auto tuning function is designed to automatically measures
the motor constants necessary for Advanced magnetic flux
vector control, Real sensorless vector control, and vector
control operation.
The motor can be run with the optimum operating
characteristics even when each motor constants differs,
other manufacturer's motor is used, or the wiring length is
long.
What is auto tuning?
1) The motor performance can be maximized.
2) Auto tuning function is recommended for improvement of motor operation performance. (Always perform auto tuning when
using Real sensorless vector control.)
3) There are two different auto tuning: offline auto tuning (measures motor constants before machine operation) and online
auto tuning (measures motor constants at every start of the inverter).
4) Tuning without motor running and with motor running are available for offline auto tuning.
5) Accuracy of speed characteristics
Online
offline (with motor running)
1)
A700
[Pr. ]
Name
71
Applied motor
80
Motor capacity
81
Number of motor poles
82
Motor excitation current 9999
83
Rated motor voltage
84
Rated motor frequency
90
Motor constant (R1)
91
Motor constant (R2)
92
Motor constant (L1)
93
Motor constant (L2)
94
Motor constant (X)
(*[Pr. 450, 453 to 463, 684, 860] are not available for
(*[Pr. 81, 91 to 94, 450, 453 to 463, 684, 859, 860] are not available for
offline (without motor running)
Initial
Setting Range
Value
0 to 8, 13 to 18, 20, 23, 24, 30, 33,
0
34, 40, 43, 44, 50, 53, 54
55K or less
0.4 to 55kW
9999
75K or more
0 to 3600kW
9999
2, 4, 6, 8, 10
9999
12, 14, 16, 18, 20
9999
55K or less
0 to 500A
75K or more
0 to 3600A
9999
200/
0 to 1000V
400V
*
60Hz
10 to 120Hz
55K or less
0 to 50
9999
75K or more
0 to 400m , 9999
55K or less
0 to 50
9999
75K or more
0 to 400m , 9999
0 to 50
55K or less
9999
0 to 3600m
75K or more
0 to 50
55K or less
9999
0 to 3600m
75K or more
55K or less
0 to 500 (0 to 100%), 9999
9999
75K or more 0 to 100
Also, tuning data (motor constants) can be copied to
another inverter with the operation panel or FR-PU07
parameter unit.
Note that a high-slip motor, high-speed motor, or other
special motor cannot be tuned. Also, the highest speed
should be 120Hz.
without tuning
By selecting a standard motor or constant torque motor, thermal
characteristic and motor constants of each motor are set.
Set the applied motor capacity.
V/F control
Set the number of motor poles.
X18 signal-ON: V/F control
V/F control
Tuning data
(The value measured by offline auto tuning is automatically set.)
Uses the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA, SF-HRCA,
SF-V5RU(1500r/min series)) constants
Set the rated motor voltage(V).
*The initial value differs according to the voltage class. (200V/400V)
Set the rated motor frequency (Hz).
,
9999
,
9999
(0 to 1000mH),
Tuning data
9999
(The value measured by offline auto tuning is automatically set.)
(0 to 400mH),
9999
9999: Uses the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA,
(0 to 1000mH),
SF-HRCA, SF-V5RU(1500r/min series)) constants
9999
(0 to 400mH),
9999
(0 to 100%), 9999
268
PARAMETER
(A700)(E700)(D700)
Description
Set 10 + number of motor poles .
.)
F700
.)
F700