Copy mode

The Basic Control Panel can store a full set of drive parameters and up to two user
sets of drive parameters to the control panel. The control panel memory is non-
volatile.
In the Copy mode, you can:
• copy all parameters from the drive to the control panel (uL – Upload). This
includes all defined user sets of parameters and internal (not adjustable by the
user) parameters such as those created by the ID Run.
• restore the full parameter set from the control panel to the drive (dL A – Download
All). This writes all parameters, including the internal non-user-adjustable motor
parameters, to the drive. It does not include the user sets of parameters.
Note: Only use this function to restore a drive, or to transfer parameters to
systems that are identical to the original system.
• copy a partial parameter set from the control panel to a drive (dL P – Download
Partial). The partial set does not include user sets, internal motor parameters,
parameters 9905...9909, 1605, 1607, 5201, nor any
MODULE
The source and target drives and their motor sizes do not need to be the same.
• copy USER S1 parameters from the control panel to the drive (dL u1 – Download
User Set 1). A user set includes
internal motor parameters.
The function is only shown on the menu when User Set 1 has been first saved
using parameter
81) and then uploaded to panel.
• copy USER S2 parameters from the control panel to the drive (dL u2 – Download
User Set 2). As dL u1 – Download User Set 1 above.
• start, stop, change the direction and switch between local and remote control.
and
Group 53: EFB PROTOCOL
9902
APPLIC MACRO
Group 51: EXT COMM
parameters.
Group 99: START-UP DATA
(see section
User parameter sets