Group 32: SUPERVISION

This group defines supervision for up to three signals from
DATA. Supervision monitors a specified parameter and energizes a relay output if
the parameter passes a defined limit. Use
relay and whether the relay activates when the signal is too low or too high.
Code Description
3201 SUPERV 1 PARAM
Selects the first supervised parameter.
• Must be a parameter number from
DATA.
• 100 =
NOT SELECTED
• 101...159 – Selects parameter 0101...0159.
• If the supervised parameter passes a limit, a relay output is
energized.
• The supervision limits are defined in this group.
• The relay outputs are defined in
OUTPUTS
(definition also specifies which supervision limit
is monitored).
LO ≤ HI
Operating data supervision using relay outputs, when LO≤HI.
• Case A = Parameter 1401
2, etc.) value is
OUTPUT
for monitoring when/if the supervised signal exceeds a
given limit. The relay remains active until the supervised
value drops below the low limit.
• Case B = Parameter 1401
2, etc.) value is
OUTPUT
Use for monitoring when/if the supervised signal falls
below a given limit. The relay remains active until the
supervised value rises above the high limit.
LO > HI
Operating data supervision using relay outputs, when LO>HI.
The lowest limit (
3203) is active initially and remains active
HI
until the supervised parameter goes above the highest limit
(
3202), making that limit the active limit. That limit remains
LO
active until the supervised parameter goes below the lowest
limit (
3203), making that limit active.
HI
• Case A = Parameter 1401
2, etc.) value is
OUTPUT
Initially the relay is de-energized. It is energized whenever
the supervised parameter goes above the active limit.
• Case B = Parameter 1401
2, etc.) value is
OUTPUT
Initially the relay is energized. It is de-energized whenever
the supervised parameter goes below the active limit.
3202 SUPERV 1 LIM LO
Sets the low limit for the first supervised parameter. See
3201
1
SUPERV
PARAM
3203 SUPERV 1 LIM HI
Sets the high limit for the first supervised parameter. See
3201
1
SUPERV
PARAM
3204 SUPERV 2 PARAM
Selects the second supervised parameter. See 3201
3205 SUPERV 2 LIM LO
Sets the low limit for the second supervised parameter. See 3204
3206 SUPERV 2 LIM HI
Sets the high limit for the second supervised parameter. See 3204
Parameters
Group 01: OPERATING
– No parameter selected.
Group 14: RELAY
1 (or 1402
RELAY OUTPUT
1
or
2
SUPRV
OVER
SUPRV
1 (or 1402
RELAY OUTPUT
1
or
SUPRV
UNDER
SUPRV
1 (or 1402
RELAY OUTPUT
1
or
2
SUPRV
OVER
SUPRV
1 (or 1402
RELAY OUTPUT
1
or
SUPRV
UNDER
SUPRV
above.
above.
Group 14: RELAY OUTPUTS
LO ≤ HI
Note: Case LO ≤ HI represents a normal hysteresis.
Value of supervised parameter
(3203)
HI
(3202)
LO
Case A
Energized (1)
RELAY
. Use
OVER
Case B
Energized (1)
RELAY
2
.
UNDER
LO > HI
Note: Case LO>HI represents a special hysteresis with
two separate supervision limits.
Value of supervised parameter
(3202)
LO
(3203)
HI
RELAY
Case A
.
OVER
Energized (1)
0
RELAY
2
.
UNDER
Case B
Energized (1)
0
1
above.
SUPERV
PARAM
2
SUPERV
PARAM
2
SUPERV
ACS550 User's Manual
Group 01: OPERATING
to define the
0
0
Active limit
above.
above.
PARAM
t
t
t
t
t
t