78

PFC macro

This macro provides parameter settings for pump and fan control (PFC) applications.
To enable, set the value of parameter 9902 to 7 (
Note: Parameter 2108
Connection example:
1...10 kohm
2
• Analog ref. and actual (AI1, 2)
• Start/stop – manual/PFC (DI1, 6)
• Run enable (DI2)
• EXT1/EXT2 selection (DI3)
• Interlock (DI4, 5)
Note: Use the following switch-on order:
1. EXT1/EXT2
2. Run Enable
3. Start.
Application macros
START INHIBIT
X1
1
SCR
Signal cable shield (screen)
2
AI1
External ref. 1 (Manual) or Ext ref. 2 (PID/PFC): 0
3
AGND
Analog input circuit common
4
10V
Reference voltage 10 V DC
5
AI2
Actual signal (PID): 4
6
AGND
Analog input circuit common
7
AO1
Output frequency: 0
8
AO2
Actual 1 (PI controller actual value): 0(4)
9
AGND
Analog output circuit common
Auxiliary voltage output +24 V DC
10 24V
Auxiliary voltage output common
11 GND
Digital input common for all
12 DCOM
13 DI1
Start/Stop (Manual): Activation starts the drive
14 DI2
Run enable: Deactivation always stops the drive
15 DI3
EXT1/EXT2 selection: Activation selects PFC control
16 DI4
Interlock: Deactivation always stops the drive
17 DI5
Interlock: Deactivation stops constant speed motor
18 DI6
Start/Stop (PFC): Activation starts the drive
19 RO1C
Relay output 1, programmable
20 RO1A
Default operation:
Running =>19 connected to 21
21 RO1B
22 RO2C
Relay output 2, programmable
Default operation:
23 RO2A
Fault (-1) =>22 connected to 24 (Fault => 22 connected to 23)
24 RO2B
25 RO3C
Relay output 3, programmable
26 RO3A
Default operation:
Auxiliary motor switched on=>25 connected to 27
27 RO3B
Input signals
PFC CONTROL
must remain in the default setting, 0 (
...
20 mA
...
20 mA
Output signals
• Analog output AO1: Frequency
• Analog output AO2: Actual 1
• Relay output 1: Running
• Relay output 2: Fault (-1)
• Relay output 3: Aux. motor ON
ACS550 User's Manual
).
OFF
...
1
10 V
Note 1.
...
...
Manual: 0
10V => 0
50 Hz
...
...
PID/PFC: 0
10V => 0
100%
PID setpoint
...
20 mA
Note 2.
The sensor needs to be powered.
See the manufacturer's instructions.
A connection example of a two-wire
sensor is shown on page 80.
Jumper setting
J1
...
AI1: 0
10 V
...
AI2: 0(4)
or
J1
...
AI1: 0
10 V
...
AI2: 0(4)
).
20 mA
20 mA

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs550-01Acs550-u1