ACS550 User's Manual
ACS550-x1-
see below
-124A-4
-125A-4
-157A-4
-180A-4
-195A-4
-246A-4
Fuses, 500...600 V drives
ACS550-U1-
see below
-02A7-6
-03A9-6
-06A1-6
-09A0-6
-011A-6
-017A-6
-022A-6
-027A-6
-032A-6
-041A-6
-052A-6
-062A-6
-077A-6
-099A-6
-125A-6
-144A-6
Emergency stop devices
The overall design of the installation must include emergency stop devices and any
other safety equipment that may be needed. Pressing STOP on the drive's control
panel does NOT:
• generate an emergency stop of the motor
• separate the drive from dangerous potential.
Input power cables/wiring
Input wiring can be any of:
• a four conductor cable (three phases and ground/protective earth). Shielding is
not required.
• four insulated conductors routed through conduit.
Input current
A
IEC 269 gG (A)
124
160
125
157
200
180
250
195
245
Input current
A
IEC 269 gG (A)
2.7
10
3.9
6.1
9.0
16
11.0
17.0
25
22.0
27
35
32
41
50
52
60
62
80
77
99
125
125
160
144
200
Input power (mains) fuses
UL Class T (A)
Bussmann type
175
JJS-175
200
JJS-200
250
JJS-250
350
JJS-350
Input power (mains) fuses
UL Class T (A)
Bussmann type
10
JJS-10
15
JJS-15
25
JJS-25
40
JJS-40
50
JJS-50
60
JJS-60
80
JJS-80
100
JJS-100
150
JJS-150
175
JJS-175
200
JJS-200
265
00467918.xls B
00467918.xls B
Technical data