Diagnostics – EFB

Fault queue for drive diagnostics

For general ACS550 diagnostics information, see chapter
The three most recent ACS550 faults are reported to the fieldbus as defined below.
0401 LAST FAULT
0412 PREVIOUS FAULT 1
0413 PREVIOUS FAULT 2

Serial communication diagnostics

Network problems can be caused by multiple sources. Some of these sources are:
• loose connections
• incorrect wiring (including swapped wires)
• bad grounding
• duplicate station numbers
• incorrect setup of drives or other devices on the network.
The major diagnostic features for fault tracing on an EFB network include
EFB PROTOCOL
descriptions
Embedded fieldbus
Value of the
Parameter
parameter that
resolution
defines 100%
0.1%
1500 rpm
0.1%
500 Hz
Modbus protocol reference
Drive parameter
parameters 5306...5309. Section
on page
98
describes these parameters in detail.
(Feedback integer) · (Parameter resolution) ·
(Value of 100% ref.) / 100% = Scaled value
1
10 · 0.1% · 1500 RPM / 100% = 15 rpm
2
100 · 0.1% · 500 Hz / 100% = 50 Hz
ABB DRV
DCU PROFILE
40401
40412
40413
ACS550 User's Manual
MOT NOM SPEED
MOT NOM FREQ
Diagnostics
on page 243.