Cooling - ABB ACS550 User Manual

Hide thumbs Also See for ACS550:
Table of Contents

Advertisement

ACS550 User's Manual

Cooling

Method
Requirement
Air flow, 208...240 V drives
The following table lists heat loss and air flow data for 208...240 V drives.
ACS550-x1-
-04A6-2
-06A6-2
-07A5-2
-012A-2
-017A-2
-024A-2
-031A-2
-046A-2
-059A-2
-075A-2
-088A-2
-114A-2
-143A-2
-178A-2
-221A-2
-248A-2
Air flow, 380...480 V drives
The following table lists heat loss and air flow data for 380...480 V drives.
ACS550-x1-
-03A3-4
-04A1-4
-05A4-4
-06A9-4
-08A8-4
-012A-4
-015A-4
-023A-4
Internal fan, flow direction from bottom to top.
Free space above and below the ACS550 drive: 200 mm (8 in).
Free space is not required on the drive's sides – ACS550 drives can be mounted
side-by-side.
Drive
Frame size
R1
55
R1
73
R1
81
R1
118
R1
161
R2
227
R2
285
R3
420
R3
536
R4
671
R4
786
R4
1014
R6
1268
R6
1575
R6
1952
R6
2189
Drive
Frame size
W
R1
40
R1
52
R1
73
R1
97
R1
127
R1
172
R2
232
R2
337
Cooling specifications
Heat loss
W
BTU/hr
189
249
276
404
551
776
973
1434
1829
2290
2685
3463
4431
5379
6666
7474
Heat loss
BTU/hr
137
178
249
331
434
587
792
1151
Air flow
3
3
m
/h
ft
/min
44
26
44
26
44
26
44
26
44
26
88
52
88
52
134
79
134
79
280
165
280
165
280
165
405
238
405
238
405
238
405
238
000467918.xls B
Air flow
3
3
m
/h
ft
/min
44
26
44
26
44
26
44
26
44
26
44
26
88
52
88
52
Technical data
283

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs550-01Acs550-u1

Table of Contents