Activate drive control functions – EFB

Controlling the drive

Fieldbus control of various drive functions requires configuration to:
• tell the drive to accept fieldbus control of the function
• define as a fieldbus input, any drive data required for control
• define as a fieldbus output, any control data required by the drive.
The following sections describe, at a general level, the configuration required for
each control function. For the protocol-specific details, see the document supplied
with the FBA module.

Start/Stop Direction control

Using the fieldbus for start/stop/direction control of the drive requires:
• drive parameter values set as defined below
• fieldbus controller supplied command(s) in the appropriate location. (The location
is defined by the Protocol Reference, which is protocol dependent.)
Drive parameter
1001
1002
1003
1
For Modbus, the protocol reference can depend on the profile used, hence two columns in these
tables. One column refers to the ABB Drives profile, selected when parameter 5305 = 0 (
LIM
parameter 5305 = 1 (
2
The reference provides direction control – a negative reference provides reverse rotation.
Value
1
10 (
EXT
COMMANDS
COMM
2
10 (
EXT
COMMANDS
COMM
3 (
DIRECTION
REQUEST
) or 5305 = 2 (
ABB DRV FULL
DCU PROFILE
Description
)
Start/Stop by fieldbus
with Ext1 selected.
)
Start/Stop by fieldbus
with Ext2 selected.
) Direction by fieldbus.
). The other column refers to the DCU profile selected when
). See section
ABB control profiles technical data
1
Modbus
protocol reference
ABB DRV
DCU PROFILE
40001 bits 0...3
40031 bits 0, 1
40001 bits 0...3
40031 bits 0, 1
2
4002/4003
40031 bit 3
ABB DRV
on page 209.
Embedded fieldbus
193