1 Alarms
1.5.1 Alarm description
100406
V.24: ASCII string too long
Scan
Serial communication via V.24
Effect
Transmission is aborted.
Explanation
Line in source file is too long; the maximum permissible length is 255 ASCII characters.
Remedy
Check the source file.
Note
Alarm from SW 6.3
100407
V.24: Invalid path
Scan
Serial communication via V.24
Effect
The file is not transferred
Explanation
The stated file path is incorrect
Remedy
Correct the path
Note
Alarm from SW 6.3
100408
V24: no write access
Scan
Serial communication via V.24
Effect
The file is not transferred
Explanation
An attempt was made to write a write–protected file
Remedy
Remove write access rights
Note
Alarm from SW 6.3
100410
V.24: no free memory available
Scan
Serial communication via V.24
Effect
The file is not transferred.
Explanation
Memory of hard disk is exhausted.
Remedy
Delete files and directories that are no longer required.
Note
Alarm from SW 6.3
100411
V.24: invalid number of digits
Scan
Serial communication via V.24: read in via punched tape
Effect
The file is not transferred
Explanation
The syntax of the file being transferred is incorrect
Remedy
Correct the file name
Note
Alarm from SW 6.3
100412
V.24: object type unknown
Scan
Serial communication via V.24: punched tape format
Effect
The file is not transferred
Explanation
An unknown object type was discovered
Remedy
Correct the data type (correct syntax must be observed, e.g. MPF, SPF, TEA1 ...)
Note
Alarm from SW 6.3
1–96
Siemens AG 2001 All rights reserved 6FC5198–jAB40
SINUMERIK 840C / SIMODRIVE 611–D (DA)
04/96