Siemens Sinamics s120 Commissioning Manual page 307

With starter
Hide thumbs Also See for Sinamics s120:
Table of Contents

Advertisement

Red flashing
light 0.5 Hz
Table 4- 3
Orange
Control Unit 320-2 DP in operation
Table 4- 4
Control Unit CU320-2 DP – Description of the LEDs after booting
LED
Color
RDY
(READY)
Green
Red
Red/
green
Orange
STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5
LED
RDY
DP
Off
Red
Red flash-
ing light 0.5
Hz
Firmware
LED
RDY
DP
Off
Alternating
State
Description, cause
OFF
Electronic power supply is missing or outside
permissible tolerance range.
Continuous
The component is ready for operation and cyclic
light
DRIVE-CLiQ communication is taking place.
Flashing
Commissioning/reset
light
0.5 Hz
Flashing
Writing to the memory card
light
2 Hz
Flashing
General errors
light
2 Hz
Flashing
Control Unit is ready for operation.
light
However, there are no software licenses.
0.5 Hz
Flashing
Updating the firmware of the DRIVE-CLiQ compo-
light
nents
0.5 Hz
Flashing
DRIVE-CLiQ component firmware update com-
light
plete. Wait for POWER ON for the components in
2 Hz
question.
State
OPT
Off
FW checked
(no CRC
error)
Off
FW checked
(CRC error)
State
OPT
Off
Initializing
Running
4.1 Diagnostics via LEDs
Comment
CRC invalid
Comment
See the table below
Remedy
Check power supply
Check parameterization /
configuration data
Obtain licenses
Turn POWER ON for the
components in question
Diagnostics
307

Advertisement

Table of Contents
loading

Table of Contents