State
RDY
DC LINK
Green/red
–
(2 Hz)
Green/
–
orange
or
red/
orange
4.1.2.9
Motor Module booksize compact format
Table 4- 22
Meaning of the LEDs on the Motor Module booksize compact
Status
RDY
DC LINK
Off
Off
Green
–
Orange
Red
Orange
Orange
Red
–
Green/red
–
(0.5 Hz)
Green/red (2
–
Hz)
Green/
–
orange
or
red/orange
See SINAMICS S120/S150 List Manual for the parameters to activate the recognition of components via LED
1)
STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5
Description, cause
Firmware download is complete. Wait for POWER ON.
Identifying whether the component is activated using the
LED (p0124)
Note:
Both options depend on the LED status when module
recognition is activated via p0124 = 1.
Description, cause
The electronics power supply is missing or outside the per-
missible tolerance range.
The component is ready for operation. Cyclic DRIVE-CLiQ
communication is taking place.
The component is ready for operation. Cyclic DRIVE-CLiQ
communication is taking place.
The DC link voltage is present.
The component is ready for operation. Cyclic DRIVE-CLiQ
communication is taking place.
The DC link voltage is outside the permissible tolerance
range.
DRIVE-CLiQ communication is being established.
This component has at least one fault.
Note:
The LED is activated regardless of whether the correspond-
ing messages have been reconfigured.
Firmware is being downloaded.
Firmware download has been completed. The system waits
for POWER ON.
Component recognition via LED is activated
Note:
Both options depend on the LED status when component
recognition is activated using the parameter.
4.1 Diagnostics via LEDs
Remedy
Carry out a POWER ON
–
Remedy
–
–
–
Check the line supply voltage.
–
Resolve and acknowledge the
fault.
–
Carry out a POWER ON.
.
–
1)
Diagnostics