Diagnostics
4.2 Diagnostics via STARTER
Starting/stopping the ramp-function generator
NOTICE
Damage to property due to unexpected movements while the function generator is active
Some monitoring functions are deactivated when the function generator is activated.
Incorrect parameterization of the function generator can result in unexpected movements of
the motor, which damage the machine.
• Do not leave the machine unattended while the function generator is active.
• Ensure that the parameter assignments are correct.
Start function generator:
1. Load the function generator.
– Click on the symbol
– In the project navigator, double-click on "Drives" > "Drive_xy" > "Commissioning" >
2. Select "Function generator as a commissioning tool".
3. Select an operating mode e.g. "Speed setpoint after filter".
4. Select a drive, for instance "SERVO_02".
5. Set a signal shape, for example, "Squarewave".
6. Click the "Assume control priority!" button.
7. For "Sign of life monitoring" click on the "Accept" button.
(the control priority button then changes to yellow).
8. Click on the symbol
9. Start the function generator by clicking on the triangle next to the red zero ( "Start
FctGen" button).
10.Carefully read the "Caution" note and confirm with "Yes".
The drive starts and executes the selected trace function.
Trace recordings are now possible.
Stopping the function generator:
1. Click on the "Stop FctGen" button.
Or
2. Click on the symbol
Parameterization
The "Function generator" parameter screen is selected with the
the STARTER commissioning tool.
344
or
"Function generator".
"Drive on".
"Drive off" in order to stop the drive.
.
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5
symbol in the toolbar of
STARTER Commissioning Manual