Preparation for commissioning

2.4 PROFINET components

2.4
PROFINET components
For communication via PROFINET, the following components are necessary:
● A communication module for PG/PC connection via the PROFINET interface.
Note
Cables that can be used for commissioning
For commissioning using the STARTER commissioning tool, the onboard Ethernet
interface of the Control Unit can be used with a crossover cable from CAT5 and higher.
The PROFINET module CBE20 supports all standard Ethernet cables and crossover
cables from CAT5/5e and higher. The crossover cable is essential for an Ethernet X127
interface.
● Connecting cable
Connecting cable between PROFINET interface and PG/PC, such as
– Industrial Ethernet FC TP Standard Cable GP 2 x 2 (up to max. 100 m)
– Industrial Ethernet FC TP Flexible Cable GP 2 x 2 (up to max. 85 m)
– Industrial Ethernet FC Trailing Cable GP 2 x 2 (up to max. 85 m)
– Industrial Ethernet FC Trailing Cable 2 x 2 (up to max. 85 m)
– Industrial Ethernet FC Marine Cable 2 x 2 (up to max. 85 m)
● Connector
Connector between the PROFINET interface and the PG/PC, for example
– Industrial Ethernet FC RJ45 Plug 145 for Control Unit
36
Standard bus cable with rigid conductors and a special design for fast installation
STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5