Parameters
The following figure illustrates parameters that can be the set for the function.
E
D
Figure 84
Pos.
Description
A
Trigger event
B
Stop delay
C
Pre-trigger
D
Frequency window
E
Recording window
Parameters that can be the set and the commands of the function are:
Parameter
Description
It selects the number of recordings (1 or 2).
Number of
dataloggers
NOTE: the recordings are independent, but they share the
sampling frequency and the type of memory.
Determines the number of data logs recorded.
Sampling
IMPORTANT:
frequency
• A high frequency allows a more accurate analysis of the
data.
• The higher the frequency, the shorter the recording.
Allows you to set the parameters and to manually command recording
number 1.
• Stop Source: it selects the trigger event, on the occurrence of which
the recording is to be stopped.
• Stop Delay: sets the delay after the trigger event after which
Datalogger 1
recording is to be stopped
• Restart command: starts recording.
• Stop command: stops the recording and saves it in memory.
IMPORTANT: the recording can only be downloaded with
the Ekip Connect application.
The selection of two recordings parameters activates additional commands :
Parameter
Description
Datalogger 2
Like Datalogger 1, but relates to recording number 2.
Restart both
Starts both the recordings.
Stop Both
It stops both the recordings and saves them in memory.
With Ekip Connect software it is possible to select the parameter volatile RAM, not available
on the display, which allows to choose whether to keep the recording also with the release off
(non-volatile) or to delete it if the auxiliary power disappears (Volatile).
NOTE: The parameter is configured by default as non-volatile.