Electrical Signalling Accessories; Aux 4Q: Auxiliary Open-Closed Contacts - ABB SACE Emax 2 Series Installation, Operation And Maintenance Instructions

Table of Contents

Advertisement

2 - Electrical signalling accessories

Aux 4Q: auxiliary open-closed
11
21
31
12
22
32
13
23
33
Q1
Q2
Q3
230 | © 2013 ABB | 1SDH001000R0002 - L7804
The Aux 4Q contacts signal the open/closed state of the circuit-breaker.
contacts
These are "switched" contacts and are available in three types:
• four standard contacts
• four digital signals (low power)
• two standard contacts + two digital signals
NOTE: The standard Aux 4Q contacts are always included in the circuit-breakers
The following table provides information on the electrical characteristics:
Characteristics
DC
41
Breaking
capacity
42
AC
43
Q4
Minimum load
Aux 4Q: Connections
Further information is available on page 156, or on the site http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
Diagram 81
Information on the assembly is available from the web site http://www.abb.com/abblibrary/
DownloadCenter/, in particular with the kit sheet 1SDH001000R0613.
Standard
24V
-
125V
0.5A @ 0ms / 0.3A @ 10ms
250V
0.3A @ 0ms / 0.15A @ 10ms
3A cos φ 0,3
250V
5A cos φ 0,7
5A cos φ 1
3A cos φ 1
2A cos φ 0,7
400V
1A cos φ 0,3
50mA @ 24V
A4
X
12
14
22
24
XV
12
14
22
24
A1
Q/1
Q/2
Q/3
XV
11
21
X
11
21
A4
Electrical accessories | 2 - Electrical signalling accessories
Digital signals
0.1 A
-
-
-
-
-
-
-
-
1mA @ 5V
81
32
34
42
44
32
34
42
44
Q/4
31
41
31
41
ABB | SACE Emax 2