Summary Table Of G Hi-Touch Protections - ABB SACE Emax 2 Series Installation, Operation And Maintenance Instructions

Table of Contents

Advertisement

Summary table of G Hi-Touch protections

ABB
ANSI
Threshold
(7)
I21 = 0.6...10 In; Step = 0.1 In
S2(V)
51V
Ul2 = 0.2...1 Un; Step = 0.01 Un
(Step)
Ks2 = 0.1...1; Step = 0.01
I21 = 0.6...10 In; Step = 0.1 In
S2(V)
Ul2 = 0.2...1 Un; Step = 0.01 Un
51V
(Linear)
Uh2 = 0.2...1 Un; Step = 0.01 Un
Ks2 = 0.1...1; Step = 0.01
Q24 = -1...-0.1 Sn; Step = 0.001 Sn
Q25 = -1...-0.1 Sn; Step = 0.001 Sn
RQ2
40/32R
(4)
Kq = -2...2; Step = 0.01;
Kq2 = -2...2; Step = 0.01
f28 = 0.4...10 Hz / s
ROCOF 81R
Step = 0.2 Hz / s
Notes
(1)
The calculation of t
is valid for values that have exceeded the activation threshold of the protection.
t
(2)
Valid tolerances with release energized in service conditions or with the auxiliary, tripping time = 100 ms, temperature and currents within operating
limits. If the conditions are not guaranteed, the tolerance of the tripping time becomes ± 20%.
(3)
The tripping threshold of the current for voltage values between Ul2 and Uh2 is calculated by performing the linear interpolation between the
thresholds Uh2 and I21 (first point on the line) and Ul2 and Ks2 * I20 (second point on the line). I
Uh2) + I21.
(5)
The power of the activation threshold of the protection RQ2 is calculated by the intersection of the 2 straight lines composed of Q24 and Kq (P
= Q
* Kq + Q24) and from Q25 and Kq2 (P
reshold
measured
applies (considering that the values are negative, the applicable threshold is the one nearest to 0).
(6)
The parameter f28 limits the selectable minimum value of t28 as follows: 0.4 s (0.4 ≤ f28 < 1 Hz / s); 0.25 s (1.2 < f28 < 5 Hz / s); 0.15 s (f28 ≥
5.2 Hz / s).
(7) ANSI / IEEE C37-2 encoding.
122 | © 2013 ABB | 1SDH001000R0002 - L7804
Tolerance
Tripping time
threshold
t21 = 0.05...30 s
± 10 %
Step = 0.01 s
t21 = 0.05...30 s
± 10 %
Step = 0.01 s
t24 = 0.5...100s
± 10 %
Step = 0.1 s
t28 = 0.15...10 s
± 10 %
Step = 0.1 s
= Q
* Kq2 + Q25). If constants Kq and Kq2 are set to 0, the higher threshold
threshold
measured
Calculation
formula
Tolerance t
t
(1)
t
The better of the two
t
= t21
values:
t
± 10% or ± 40 ms
The better of the two
t
= t21
values:
(3)
t
± 10% or ± 40 ms
The better of the two
t
= t24
values:
t
± 10% or ± 40 ms
The better of the two
(5)
t
= t28
values:
t
± 10% or ± 40 ms
= [(I21 * Ks2 *I20) / (Uh2 * Ul2)] / (U
threshold
Ekip Touch protection release | 13 - G Hi-Touch protections
ABB | SACE Emax 2
(2)
t
*
measured
th-

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sace emax e2.2Sace emax e4.2Sace emax e6.2

Table of Contents