20 - Default parameters

Ekip TOUCH default parameters The Ekip Touch releases are supplied with the following default parameters:
149 | © 2013 ABB | 1SDH001000R0002 - L7804
Protection/Parameter
L
S
(2)
I
MCR
G
(2)
IU
OT
Current thresholds
Current thresholds
Harmonic Distortion
Gext
(2) (3)
Rc
(3)
Frequency
Neutral
Datalogger
Power Controller
Hardware Trip
Monitor Time
Local bus
Alive LED
Language
Password
Mode
Modbus RTU par
Profibus par
Devicenet
Modbus TCP
(1)
Thermal memory, startup, Zone selectivity set to Off.
(2)
Protection S available with LSI and LSIG versions of the release. Protection G available with LSIG version.
(3)
Protections available in the presence of the respective sensors.
(4)
Protection activated on request when purchasing the release.
The protections activated by the presence of the Ekip Measuring Pro module, have the following
default parameters:
Protection/Parameter
VU
UV
OV
UF
OF
RP
Phase Sequence
Cos φ
Value
(1)
1 In; 144 s; Prealarm: 90 %
Off; 2 In; 50 ms; Curve: t = k
4 In
Off; 6 In; 40 ms
Off; 0.25 In; 400 ms; Curve: t = k
Off; 50%; 5 s
Off
Off; 1: 50 %; 2: 75 %
Off; Iw1: 3 In; Iw2: 3 In
On
Off; 0.25 In; 400 ms; Curve: t = k
Off; 3 A; 60 ms
50 Hz
Off (for CB 3 P)
50% (for CB 4 P)
Off
see note
(4)
Disabled
5 min
Disabled
Disabled
English
00001
Local
Address: 247; baudrate: 19.2 Kb
Address: 2
MAC ID: 63; baudrate: 125 Kb
Static IP: 0.0.0.0
Value
Off; 50%; 5 s
Off; 0.9 Un; 5 s
Off; 1.05 Un; 5 s
Off; 0.9 fn; 3 s
Off; 1.1 fn; 3 s
Off; 0.1 Sn; 10 s
123
Off; 0.95
Ekip Touch protection release | 20 - Default parameters
ABB | SACE Emax 2
Continued on the next page