Access from the display To configure the module the release must be on. Then the presence of the module activates
180 | © 2013 ABB | 1SDH001000R0002 - L7804
the additional menus on the display:
• In order to configure the inputs and output contacts.
• To display information on the module and the state of inputs and outputs.
The following table illustrates the path for accessing the configuration parameters of the
module from the display:
...
Network frequency
Settings
Modules
Power Controller
...
(1)
Like the menu I 01.
(2)
Like the menu O 01.
NOTE: the module can also be configured the Ekip Connect application (see the
chapter "13 - Other accessories", and the paragraph "Ekip Connect application" on
page 221).
The following table illustrates configuration parameters of the inputs:
Parameter
Selectable values
Active open, Active
Polarity
closed
00...100.00 s
Delay
in steps of 0.01 s
Local/Remote
Local Bus
...
I 01
I 02
I 03
I 04
Ekip Signalling 4K
O 01
O 02
O 03
O 04
...
Function
Default
Description
• Active open = To be considered
active, the input must be floating.
Active
• Active closed = To be considered
closed
active, the input must be connected
to its reference.
Standby time after that the input
has changed state, before the
change of state is recognised (if the
input is reset before a time equal to
0.01 s
the delay has elapsed, the change
of state is nor recognised). If 0.00
s is selected, the value 300 μs is
assigned to the parameter.
Electronic accessories | 4 - Ekip Signalling 4K module
ABB | SACE Emax 2
Polarity
Delay
(1)
(1)
(1)
Signal source
Delay
Contact Type
Self-latching
min Activation Time
(2)
(2)
(2)
Continued on the next page