Table of Contents

Advertisement

Dimensions Information on the overall dimensions is available on the web site http://www.abb.com/
Phase separators Phase separators are available on request. Alternatively, it is possible to position the insulation
28 | © 2013 ABB | 1SDH001000R0002 - L7804
Continued from the previous page
IMPORTANT: before proceeding with the connection between terminals and
connection busbars:
• make sure that contact surfaces of the busbars are free of burrs, dents,
traces of rusting, dust or traces of grease.
• make sure, if aluminium busbars are used, than these are tin plated in the
contact areas.
• make sure that the busbars do not exert forces in any direction on the
terminal.
• for tightening use M12 screws with resistance class 8.8 equipped with
spring washers and lock them with a torque of 70 Nm.
NOTE: Information on the performance of the circuit-breakers in the switchgear in
the various configurations is available from the web site http://www.abb.com/abblibrary/
DownloadCenter/, in particular with the Emax 2 catalogue 1SDC200023D0201.
abblibrary/DownloadCenter/, in particular with the Emax 2 catalogue 1SDC200023D0201.
The following drawings are also available in .dxf format:
1SDH001000R0100
- E2.2 III-IV Fixed HR VR
- E2.2 III-IV Fixed F
1SDH001000R0101
1SDH001000R0102
- E2.2 III-IV Withdrawable HR-VR
1SDH001000R0103
- E2.2 III-IV Withdrawable F
1SDH001000R0104
- E2.2 III-IV Fixed SHR
1SDH001000R0105
- E2.2 III-IV Withdrawable SHR
- E2.2 III-IV Fixed SVR
1SDH001000R0106
1SDH001000R0107
- E2.2 III-IV Withdrawable SVR
1SDH001001R0100
- E4.2 III-IV Fixed HR VR
1SDH001001R0101
- E4.2 III-IV Fixed F
1SDH001001R0102
- E4.2 III-IV Withdrawable HR-VR
- E4.2 III-IV Withdrawable F
1SDH001001R0103
1SDH001060R0100
- E6.2 III-IV Fixed HR
1SDH001060R0101
- E6.2 III-IV Fixed VR
- E6.2 IV FS Fixed HR-VR
1SDH001060R0102
1SDH001060R0104
- E6.2 III-IV Fixed F
1SDH001060R0105
- E6.2 III-IV Withdrawable HR
1SDH001060R0106
- E6.2 III-IV Withdrawable VR
1SDH001060R0107
- E6.2 IV FS Withdrawable HR-VR
- E6.2 III-IV Withdrawable F
1SDH001060R0108
1SDH001000R0120
- E2.2-E4.2-E6.2 Fixed Withdrawable Flange
1SDH001000R0121
- E2.2-E4.2-E6.2 Fixed internal mounting
barriers to segregate live parts.The Phase separators are mandatory if, between two phases,
the minimum distance between the mounting screws of the circuit-breaker terminals with the
connection bars is less than 14 mm.
Information on the assembly is available from the web site http://www.abb.com/abblibrary/
DownloadCenter/, in particular with the kit sheet 1SDH001000R0810.
ABB | SACE Emax 2
Emax E2.2-E4.2-E6.2 circuit-breakers | 6 - Installation

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sace emax e2.2Sace emax e4.2Sace emax e6.2

Table of Contents