Aux 15Q: External additional
open/closed auxiliary contacts The external additional Aux 15Q contacts signal the open/closed state of the circuit-breaker.
232 | © 2013 ABB | 1SDH001000R0002 - L7804
These are "switched" contacts and are available in two types:
• 15 standard contacts
• 15 digital signals (low power)
The following table provides information on the electrical characteristics:
Characteristics
DC
Breaking
capacity
AC
Minimum load
Aux 15Q external: Connections
Further information is available on page 156, or on the site http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
202
204
212
Q/11
Q/12
201
A4
282
284
292
Q/19
Q/20
281
Diagram 91
Information on the assembly is available from the web site http://www.abb.com/abblibrary/
DownloadCenter/, in particular with the kit sheet 1SDH001000R0607.
Standard
24V
-
125V
0.5A @ 0ms / 0.3A @ 10ms -
0.3A @ 0ms / 0.15A @
250V
10ms
3A cos φ 0,3
5A cos φ 0,7
250V
5A cos φ 1
3A cos φ 1
400V
2A cos φ 0,7
1A cos φ 0,3
50mA @ 24V
214
222
224
232
234
242
Q/13
Q/14
Q/15
211
221
231
294
302
304
312
314
322
Q/21
Q/22
Q/23
291
301
311
Electrical accessories | 2 - Electrical signalling accessories
ABB | SACE Emax 2
Digital signals
0.1 A
-
-
-
-
-
-
-
1mA @ 5V
244
252
254
262
264
272
Q/16
Q/17
Q/18
241
251
261
324
332
334
342
344
Q/24
Q/25
321
331
341
91