Access from the display With the modules powered, and Local Bus enabled, the presence of the modules on the
199 | © 2013 ABB | 1SDH001000R0002 - L7804
terminal box activates additional menus on the display, to configure the modules according to
the characteristics of the network.
To enable the Local Bus, you need to select "On" in the menu Settings, Modules, Local Bus.
The following table illustrates the path for accessing the configuration parameters of the
modules from the display:
...
Network frequency
Settings
Modules
Power Controller
...
NOTE: the modules can also be configured with the Ekip Connect application (see
the chapter "13 - Other accessories", and the paragraph "Ekip Connect application"
on page 221).
The default serial address is 2 for the Ekip Com Profibus, and 3 for the Ekip Com Profibus
Redundant, and can be modified with a value between 1 and 125.
IMPORTANT: devices connected to the same network must have different
addresses.
The following table illustrates the path from the display for accessing information on the
modules:
Protection unit
Circuit-breaker
Information
Modules
Power Controller
The information on the modules that can be viewed includes the serial number and the software
version.
Local/Remote
Local Bus
...
Ekip Com Profibus
Serial address
Ekip Com Profibus *R
Serial address
...
Function
...
Ekip Com Profibus
Ekip Com Profibus *R
...
Electronic accessories | 7 - Ekip Com Profibus modules
ABB | SACE Emax 2