ABB SACE Emax 2 Series Installation, Operation And Maintenance Instructions page 164

Table of Contents

Advertisement

160 | © 2013 ABB | 1SDH001000R0002 - L7804
Continued from the previous page
SR
Push-button or contact for electrical reset of the break contact S51
Input for zone selectivity for protection S or input in "inverse" direction for
SZi(DFi)
protection S
Output for zone selectivity for protection S or output in "direct" direction for
SZo(DFo)
protection D
TI / L1
Current transformer, phase L1
TI / L2
Current transformer, phase L2
TI / L3
Current transformer, phase L3
TI / N
Current transformer on the neutral
TU1...TU2
Isolation voltage transformer (external to the circuit-breaker)
Uaux
Auxiliary power supply voltage
UI / L1
Current sensor, phase L1
UI / L2
Current sensor, phase L2
UI / L3
Current sensor, phase L3
UI / N
Current sensor on the neutral
UI / O
Homopolar current sensor
W2
Serial interface with the internal bus (local bus)
W9...W13
RJ45 connector for communication modules
W9R...
RJ45 connector for redundant communication modules
W11R
Delivery connector for the auxiliary circuits of the circuit-breaker in
X
withdrawable version
XB1...XB7
Connectors for the circuit-breaker applications
Delivery terminal box for the position contacts of the circuit-breaker in
XF
withdrawable version
XF1...XF2
Contact of the Ekip protection release for activation of the fans
XK1...XK3
Connectors for the auxiliary circuits of the Ekip protection release
XK7
Connector for the auxiliary circuits of the communication modules
Delivery terminal box for the auxiliary circuits of the circuit-breaker in fixed
XV
version
YC
Closing coil
YC2
Second closing coil
YO
Opening coil
YO1
Opening coil for overcurrent
YO2
Second opening coil
YR
Coil for electrical reset of the break contact S51
YU
Under-voltage coil
The following is a key to the notes used in the wiring diagrams:
Note
Description
A)
The auxiliary power supply for the Ekip release is obligatory
C)
Always supplied with the Ekip Com module.
D)
Always supplied with the motor for loading the closing springs (diagram 13)
Voltage transformer, mandatory in the case of external outlet sockets.
E)
External outlet sockets, mandatory for systems with rated voltage greater
than 690V.
The connections between the residual-current protection RC sensor and
the poles of connector X (or XV) of the circuit-breaker must be implemented
F)
with a screened two-pole cable with paired braided conductors (BELDEN
9696 paired type or equivalent), with length no greater than 10m. The
screen must be earthed on the circuit-breaker side.
ABB | SACE Emax 2
Continued on the next page
Accessories | 2 - Wiring diagrams

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sace emax e2.2Sace emax e4.2Sace emax e6.2

Table of Contents