Table of Contents

Advertisement

M: motor

U1
U2
M
229 | © 2013 ABB | 1SDH001000R0002 - L7804
The motor automatically recharges the closing springs of the circuit-breaker when these are
discharged.
The motor is equipped with a limit contact S33 M/1 that interrupts the power supply of the
motor after loading of the springs is completed.
The motor is equipped with a limit contact S33 M/2 that signals the state of the loaded
springs.For information on the S33 M/2 limit contact refer to the dedicated paragraph "S33
M/2: springs loaded signalling contact" in this chapter.
NOTE: In the absence of power supply, the closing springs can in any case be loaded
manually through the appropriate front control lever.
The tables listing the available voltages and the electrical characteristics are provided
below:
Available voltages (Un)
24V...30V AC/DC
48V...60V AC/DC
100V...130V AC/DC
220V...250V AC/DC
380V...400V AC
440V...480V AC
M: Connections
Further information is available on page 156, or on the site http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
Diagram 13
Information on the assembly is available from the web site http://www.abb.com/abblibrary/
DownloadCenter/, in particular with the kit sheet 1SDH001000R0609.
General characteristics
Operating limits (Standards
IEC60947-2)
Inrush power (Ps)
Continuous power (Pc)
Charging time
13
+
A4
~
X
U1
XV
U1
XB1
1
S33M/1
A1
F1
M
XB1
2
XV
U2
X
U2
-
A4
~
Electrical accessories | 1 - Electrical Control accessories
ABB | SACE Emax 2
85%...110% Un
AC= 500VA DC= 500W
AC= 100VA DC= 100W
7 sec

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sace emax e2.2Sace emax e4.2Sace emax e6.2

Table of Contents