5 - Environmental conditions

Installation environment Install the circuit-breaker in a dry environment, without dust or corrosive acids, and so that is
Temperatures of the installation
environment
Particular weather conditions The circuit breaker is designed to operate in particularly difficult industrial environments.
Dusty environments It is recommended to install the circuit breaker in suitably ventilated switchgear where
22 | © 2013 ABB | 1SDH001000R0002 - L7804
not subject to shock or vibration.
If this is not possible, mount the circuit-breaker in a framework protecting it adequately.
For the dimensions to be considered for installation, see the chapter "6 - Installation" on page
24 where the following information can be found:
• minimum installation volumes of the circuit-breakers and derived versions
• distances to be respected for circuit breakers in a cell
• overall dimensions of the circuit breakers
• drilling of mounting holes
• drilling of the cell door
The mechanical and electrical characteristics are guaranteed between -25 ° C and +70 ° C.
It was tested according to:
• IEC 60068-2-1: endurance at low temperatures
• IEC 60068-2-2: hot dry climate
• IEC 60068-2-30: hot humid climate
• IEC 60068-2-52 severity 2: saline mist atmosphere
• IEC 60947 (pollution level ≤ 3)
• IEC60721-3-6 class 6C3
• IEC60721-3-2 class 3C2
NOTE: the circuit-breaker is suitable for installation in environments with saline
concentrations no higher than 10 mg/m3.
penetration by dust is minimized.
If the environments are dusty (dust> 1mg/m3) it is required to always follow the second level
maintenance procedures.
Vibration The circuit-breaker is insensitive to mechanical or electromagnetic vibrations that meet the
following standards:
• IEC 60068-2-6 a) From 1 to 13Hz with movement equal to 1mm b) From 13 to 100Hz
with constant acceleration equal to 0.7g
• Naval specifications: RINA, BV, GL, ABS, LRs, DNV
Emax E2.2-E4.2-E6.2 circuit-breakers | 5 - Environmental conditions
ABB | SACE Emax 2