Connections The modules must be mounted on the terminal box of the circuit-breaker or of the fixed part of
Termination resistor The modules provide the possibility to insert a 120 Ω termination resistor on the RS-485 bus,
202 | © 2013 ABB | 1SDH001000R0002 - L7804
the withdrawable circuit-breaker, in the first free slot after the Ekip Supply module.
Information on the assembly is available from the web site http://www.abb.com/abblibrary/
DownloadCenter/, in particular with the kit sheet 1SDH001000R0512.
The wiring diagrams for the modules are included below:
61
71
81
91
01
51
95
35
R1
V3
HC
H1
H2
H3
H4
62
72
82
92
02
U1
52
96
36
R2
V2
HC
K3
K4
K5
K6
64
74
84
94
04
54
98
38
U2
V1
HC
K7
K8
K9
K10
Q5..Q10
EKIP Signalling 4K
S51
S33
M
YR
A4
X
XV
A3
XV
X
A4
* L), * M)
Diagrams 55 - 65
Further information is available on page 156, or on the site http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
by setting the dip-switches Rterm on the side of the modules, in position on. This option must
be selected before the installation of the modules.
For the positions on and off of the dip-switches Rterm, see the following figure (on DeviceNet
communication modules, the remaining dip-switches are not used).
Figure 90
Vn
Ge
Szi
Rct
Ge-
Szo
Gzo
Szc
Gzi
Trip Unit I/O
Module
Module
Module
55
O)
*
S75I/5
XK7
1
XK7
2
K51
K51
COM
COM
W7
W8
W7
W8
(H)
(L)
BUS 1
* L), * M)
Electronic accessories | 8 - Ekip Com DeviceNet modules
ABB | SACE Emax 2
Ne-
45
D1
C1
C11
C21
11
21
Ne
46
C3
C13
12
22
W3
K1
W4
K2
Rca
48
D2
C2
C12
C22
14
24
YU
TU
EKIP Supply
RTC
YC
YO
YC2
Q1
Q2
I/O
YO2
65
W7R
W8R
W7R
W8R
(H) (L)
BUS 2
ON
1 2 3 4
31
41
32
42
34
44
Q3
Q4
A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sace emax e2.2Sace emax e4.2Sace emax e6.2

Table of Contents