Aux 6Q: Additional open/closed
auxiliary contacts
61
71
81
91
51
HC
H1
H2
H3
62
72
82
92
52
HC
K3
K4
K5
64
74
84
94
54
HC
K7
K8
K9
Q5..Q10
EKIP Signalling 4K
231 | © 2013 ABB | 1SDH001000R0002 - L7804
The additional Aux 6Q contacts signal the open/closed state of the circuit-breaker.
These are "switched" contacts and are available in two types:
• six standard contacts
• six digital signals (low power)
NOTE: it is possible to order the Aux 6Q contacts only if the circuit-breaker is not
equipped with a protection release with the Ekip Signalling 4K module.
The following table provides information on the electrical characteristics:
Characteristics
DC
Breaking
capacity
01
AC
H4
02
K6
04
K10
Minimum load
Aux 6Q: Connections
Further information is available on page 156, or on the site http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
A4
X
XV
A1
XV
X
A4
Diagram 1
Information on the assembly is available from the web site http://www.abb.com/abblibrary/
DownloadCenter/, in particular with the kit sheet 1SDH001000R0601.
Standard
24V
-
125V
0.5A @ 0ms / 0.3A @ 10ms
250V
0.3A @ 0ms / 0.15A @ 10ms -
3A cos φ 0,3
250V
5A cos φ 0,7
5A cos φ 1
3A cos φ 1
2A cos φ 0,7
400V
1A cos φ 0,3
50mA @ 24V
52
54
62
64
72
74
52
54
62
64
72
74
Q/5
Q/6
Q/7
51
61
71
51
61
71
ABB | SACE Emax 2
Digital signals
0.1 A
-
-
-
-
-
-
-
1mA @ 5V
82
84
92
94
02
04
82
84
92
94
02
04
Q/8
Q/9
Q/10
81
91
01
81
91
01
Electrical accessories | 2 - Electrical signalling accessories