ABB SACE Emax 2 Series Installation, Operation And Maintenance Instructions page 181

Table of Contents

Advertisement

177 | © 2013 ABB | 1SDH001000R0002 - L7804
Continued from the previous page
The following table illustrates configuration parameters of the module:
Parameter
Values
100 V, 115 V, 120 V, 190 V,
208 V, 220 V, 230 V, 240 V,
277 V, 347 V, 380 V, 400 V,
Primary Voltage
415 V, 440 V, 480 V, 500 V,
550 V, 600 V, 660 V, 690 V,
910 V, 950 V, 1000 V, 1150 V
Secondary
100 V, 110 V, 115 V, 120 V
Voltage
Concatenated
V12, V23, V31
Ref
NO Contact
No, Yes
The following table illustrates the path from the display to view information on the module and
synchronism status:
Protection unit
Circuit-breaker
Information
Modules
Power Controller
The information that can be displayed is as follows:
• The serial number and the software version.
• The overall synchronism status ("Ok" or "Not OK").
• The correspondence between the voltage, frequency, and phase values ("Ok" or "Not OK").
Default
Description
Primary voltage of the
100 V
isolation transformer.
Secondary voltage of the
100 V
isolation transformer.
Input phase-to-phase voltage
V12
to the module.
Status of the contact:
Yes
• No = Normally closed.
• Yes = Normally open.
...
Ekip Synchrocheck
...
Electronic accessories | 3 - Ekip Synchrocheck module
ABB | SACE Emax 2