Advertisement

Commissioning
5.5 First commissioning with the AOP30
Note
Enter the motor-side filter
A filter on the motor side must be entered in p0230:
• Option L07 – dv/dt filter compact plus Voltage Peak Limiter: p0230 = 2
• Option L08 – motor reactor: p0230 = 1
• Option L10 – dv/dt filter plus Voltage Peak Limiter: p0230 = 2
• Option L15 – sine-wave filter: p0230 = 3
When p0230 = 4 "External sine-wave filter", a separate sine-wave filter can be entered. An
input mask for specific filter data then appears.
NOTICE
Damage to the sine-wave filter if it is not activated during commissioning
The sine-wave filter may be damaged if it is not activated during commissioning.
• Activate the sine-wave filter during commissioning.
NOTICE
Damage to the dv/dt filter if it is not activated during commissioning
The dv/dt filter may be damaged if it is not activated during commissioning.
• Activate the dv/dt filter during commissioning.
Note
Motor reactor
If a motor reactor (option L08) is being used, the option selection must be activated,
otherwise the closed-loop motor control will not be able to operate in an optimum fashion.
Note
Do not use a selection
The choice "no selection" is also available as default setting for the command and setpoint
sources; if selected, no default settings are applied for the command and setpoint sources.
250
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A